ENGINEERING
SPECIFICATIONS FOR MB SERIES F.R.P. COOLING TOWERS
COOLING TOWERS - Furnish and install
Aqua-Loop Model MB ______, factory or on site assembled, induced draft, counterflow,
vertical air discharge. Overall dimensions shall not exceed feet _____
in diameter and overall height not to exceed approximately ____ feet. The operating weight
shall not exceed _____ pounds.
PERFORMANCE - Unit shall have capacity to
cool _____ GPM of water from _____ºF to _____ ºF with _____ ºF entering wet-bulb
temperature. Performance of cooling tower shall be manufacturer tested in accordance with
C.T.I. Acceptance Test Code ATC-105.
CASING AND COLD WATER BASIN - Casings and
cold water basin shall be constructed of non-ferrous, high strength, quality fiberglass
reinforced polyester (F.R.P.) with ultra-violet (U.V.) stabilized and exterior gel-coated
for long-life and durability. Design shall provide quick removal of single casing section
for total access to all components of tower for maintenance and service. Standard
accessories in the cold water basin shall be all non-ferrous materials of P.V.C., F.R.P.,
A.B.S., stainless steel and brass.
AIR INLET LOUVERS - Inlet louvers shall be
fiberglass polyester (F.R.P.). The design shall minimize inlet air resistance, prevent
water splash-out during operation and under high wind conditions; minimize direct sunlight
entry to prevent bacterial growth environment; and reduce water-splash noise in rain zone
below fill from leaving the tower. Design shall also provide quick inlet section removal
for total access to cold water basin.
DRIVER SYSTEM - Fan motor shall be U.L.
Standard, (TEAO) for Models up to
MB-50, (TEFC) for Models up to MB-60, weather-proof, and suitable for outdoor service on
_____ volts, _____ Hz and _____ phase. Motor shall be direct drive up to Model MB-50 and
belt driven at Models MB-60 - 1250. Reducers on belt drive models shall be totally sealed
and no maintenance required.
FAN SYSTEM - Fan shall be heavy duty, axial
flow type with wide, light-weight aluminum alloy airfoil design blades. Fan to revolve in
F.R.P. unique design cylinder to maximize fan efficiency at low revolutions, with super
low noise levels, and provide optimum air quantity CFM. Models MB-125 and up shall be
adjustable pitch fan to further minimize power consumption.
DISTRIBUTION SYSTEM - The system shall have
non-ferrous P.V.C. sprinkler arms jointed to rotating plastic A.B.S. or copper alloy
sprinkler heads mounted onto P.V.C. stand pipe. The system shall provide even water
distribution at optimum pump head, and discharge its water immediately over FILL
preventing excessive drift (carry-over). Models MB-90 and up shall provide F.R.P. drift
eliminators over-sprinkler arms with tension bars made from hot-dipped galvanized steel.
Aqua Loop Page (3) Continuation
WET DECK (FILL) - The cooling tower FILL
shall be rigid P.V.C. (Poly-Vinyl Chloride) and be resistant to rot, decay or biological
attack, and be self-extinguishing for fire resistance with flame spread rating of 5 per
ASTM-E84-8la. Fill surface shall be state-of-the-art to induce turbulent mixing between
air and water to maximize heat and moisture transfer.
All models shall contain P.V.C. fill to withstand up to 130 ºF water temperature.
Applications requiring higher temperatures shall provide C.P.V.C. as an option.
SUPPORT COMPONENTS - (1) Support for motor,
fan, reducer, fan guard, tension bars and fills shall be hot-dipped galvanized steel.
Tower supports on Models MB-60, 80, 200 and up shall be hot-dipped galvanized steel; tower
supports on all other models to be F.R.P. All fasteners shall be stainless steel. Tower
shall be designed to withstand 100 m.p.h. wind speed and wind load of approximately 30
pounds per square foot.
LADDERS (1) - Models MB-50 and up shall
include a hot-dipped galvanized steel ladders for access to mechanical components.
GUARANTEE AND WARRANTY
PERFORMANCE - Thermal performance on MB
Series shall be as specified and guaranteed by AQUA-LOOP COOLING TOWERS COMPANY.
CUSTOMER SERVICE- AQUA-LOOP COOLING
TOWER COMPANY personnel shall make every effort to ensure each project order is
completed promptly and accurately.
TECHNICAL SUPPORT AND
MAINTENANCE - AQUA-LOOP COOLING TOWER COMPANY
provides technical support services through our Representatives for all Cooling
Tower applications. Maintenance and inspections are available upon request.
EQUIPMENT WARRANTY - AQUA-LOOP’s
F.R.P. Round Cooling Tower shall carry a Five (5) Year Manufacturer
Limited Warranty (2). Electrical motor Manufacturer shall warrant motors at a
minimum of One (1) Year.
(1) Can be supplied in Stainless Steel upon request.
(2) Does not include improper or negligent use of product or any act of
nature such as floods, tornadoes, earthquakes, or any other such Acts of God.